ACR3933 - 1ST ASSIGNMENT

Kindly size up the units using CLTD.

Area (UPS room): 1st floor (27 sqm, ceiling height 3m) x N + 1 air-cooled wall mounted split unit
Room requirement: RH 45% +- 10%; 21 deg C +- 1 deg C
Design criteria:
lighting: 20W / sqm
occupancy: 90W sensible & 40W latent
Small power load: 40W/sqm
Heat load 60 kVA UPS
16 L/s /person
10 sqm/person

air movement should be maximum 0.25m/s at 1800mm

Deadline for submission: 8/8/07, 8.30a.m

4 comments:

Firdaus said...

Sir,

Regarding about assignment, CLTD Method required to use U-factor, so is it any data on wall u-factor. in your question mention about : air movement should be maximum 0.25m/s at 1800mm, what mean by 1800mm?infiltration?

Thanks,

Nor Firdaus Yunus
ACIR 7
0124840079
nor_firdaus@yahoo.com

chookhean said...

You can use any data for U-factor, as long as you mentioned in your submission.
The 1800mm is the height to have that air movement.

farid said...

Sir,

What is the "N+1" means? Is it facing 'north' or something else?

Regards,

Ahmad Farid
ACIR7

chookhean said...

N means number of duty units + 1 means 1 standby unit.
If you need 3 duty units, meaning that you have to install 3 units (N) as duty and 1 standby unit.